Advertisement

1MRK 505 406-UEN B
the incidence of a fault, as a consequence of incorrect switching and when CT saturation takes
place. Since the currents during power swings are sinusoidal and do not contain a DC
component, it is permissible to assume that the problem of CT saturation does not arise.
Zero-crossings resulting from the slip are in any event excluded by the current enable setting
of I
.
min
5.2
Definite time over- and undercurrent protection 51
(OCDT)
5.2.1

Mode of operation

Over- and undercurrent function for:
phase fault protection
backup protection
or for monitoring a current minimum
5.2.2

Features

Insensitive to DC component
Insensitive to harmonics
Single or three-phase measurement
Maximum respectively minimum value detection in the three-phase mode
Detection of inrush currents
5.2.3

Inputs and outputs

5.2.3.1

CT/VT inputs

Current
5.2.3.2

Binary inputs

Blocking
5.2.3.3

Binary outputs

Pick-up
Tripping
5.2.3.4

Measurements

Current amplitude
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved
Section 5
Bay protection functions
GUID-01B16DD6-3FA9-4079-9390-9204C842DAD9 v1
GUID-0F07ECF4-7210-44FF-A17D-97F403D140FB v1
GUID-F644DFAA-0B84-4353-9F19-FE8FD67FE590 v1
GUID-AB3D1639-2EDC-4AE9-BE1B-DD3EA05AA4F9 v1
GUID-C0E2CC33-55E1-4C4F-84A0-CD307A90DA0A v1
GUID-AFB5BC3C-9DB7-450E-9C49-4CB7196297F7 v1
91

Advertisement

Table of Contents
loading

Table of Contents