Configuration; Operation Of The Function Without Integration - ABB RELION REB500 Technical Manual

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 406-UEN B
5.12.6

Configuration

5.12.6.1

Operation of the function without integration

Start
Impulse prolongation
Tripping
Impulse prolongation
IEC19000470 V1 EN-US
Figure 66: Operation of the delay function without integration
Bay protection functions REB500
Technical manual
t
R
0
0
t
A
0
Start
0
0
t
A
Tripping
0
Tripping only takes place, if a start also occurs within the time t
t
tripping time (
A
t
reset time (
R
© Copyright 2019 ABB. All rights reserved
0
t
t
0
(No tripping)
0
t
t
R
0
t
t
0
(No tripping)
t
0
Trip-Delay )
Reset-Delay )
Bay protection functions
GUID-BE6B0E31-83CE-4C88-ABCC-0BA8078CA6D6 v1
t
t
R
R
t
t
t
A
(No tripping)
t
t
t
R
R
t
t
t
A
t
18000065-IEC19000470-1-en.vsdx
.
R
Section 5
177