ABB RELION REB500 Technical Manual page 79

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 406-UEN B
Permissive underreaching transfer tripping (PUTT)
The criteria for tripping and transmission of a transfer trip signal by the distance protection
function in a PUTT scheme are given in the tabular overview below.
t = Delay (1)
= 0 sec :
t = Com Rec :
t = Delay (2) :
t = Delay (3) :
t = Delay (Def) :
IEC19000426 V1 EN-US
PUTT transmit logic (PUTT_SEND)
The logic (PUTT_SEND) transfers its output signals to a common transmit logic for PUTT,
POTT and BLOCK OR schemes.
PUTT NONDIR
PUTT FWD
PUTT OR
DELAY3
MEAS MAIN
START LIL2L3
IEC19000427 V1 EN-US
Figure 25: PUTT_SEND segment
Table 57:
Signal
PUTT_NONDIR
PUTT_FWD
PUTT_OR
DELAY3
MEAS_MAIN
START_L1L2L3
PUTT_ON
PUTT_SEND
Bay protection functions REB500
Technical manual
Trip
Send
Trip (PUTT NONDIR)
Trip (PUTT FWD)
Trip (PUTT OR2)
Send
Trip
Send
Trip
Send
Trip
Send
OR
18000024-IEC19000427-1-en.vsdx
Signals PUTT_SEND (see above diagram)
In
X
X
X
X
© Copyright 2019 ABB. All rights reserved
= Meas Main
= Meas Main
= Com Rec * (Start L1+L2+L3 + Weak)
= Com Rec * Meas Fward
= (Com Rec + Unblock) * Meas Oreach
= Meas Main
= Meas Main
= Meas Main
= Meas Main
= "0"
= Start L1+L2+L3 (dir/nondir)
= "0"
PUTT ON
AND
PUTT SEND
Out
Source
Setting: Com Mode
PUTT non-directional
PUTT_NONDIR = 1
PUTT Forwards: PUTT_FWD = 1
: PUTT_BWD = 1
PUTT OR2
Binary output: Delay 3
Binary output: Meas Main
Binary output: Start L1+L2+L3
X
X
Bay protection functions
GUID-666A852F-90EE-4C7D-BF10-B16BFE5DDD69 v1
GUID-DBE31BF6-F8DB-4CE9-90F5-A256D838FC8D v1
Drain
:
Internal signal to the
distance function
transmit logic
(SENDLOGIC)
Internal signal to the
distance function
transmit logic
Section 5
73