ABB RELION REB500 Technical Manual page 82

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 5
Bay protection functions
t = Delay (1)
= 0 sec :
t = Com Rec :
t = Delay (2) :
t = Delay (3) :
t = Delay (Def) :
IEC19000429 V1 EN-US
POTT transmit logic (POTT_SEND)
P_PO TT
MEAS_OR2
BIT_TBE
DELAY2
P_ECHO
MEAS_BWD
M_OWN
EXTBLK_HF
HFREC
IEC19000430 V1 EN-US
Figure 27: POTT_SEND segment
Table 59: Signals POTT_SEND
Signal
P_POTT
MEAS_OR2
BIT_TBE
DELAY2
P_ECHO
MEAS_BWD
M_OWN
Table continues on next page
76
Trip
= Meas Main
Send
= Meas Oreach * notTransbl
Trip
= (Com Rec + Unblock) * Meas Oreach * notTransbl
Trip Weak
= Com Rec * Weak * notMeas Bward * notMeas Oreach
Send
= Meas Oreach * notTransbl
Send Echo
= Com Rec * notMeas Bward
Trip
= Meas Main
Send
= "0"
Trip
= Meas Main
Send
= "0"
Trip
= Start L1+L2+L3 (dir/nondir)
Send
= "0"
AND
OR
100
AND
150
AND
AND
In
Out
X
X
X
X
X
X
X
© Copyright 2019 ABB. All rights reserved
POTT_ON
AND
OR
POTT_SEND
AND
18000026-IEC19000430-1-en.vsdx
Source
Setting: Com Mode
POTTP_POTT= 1
Binary output: Meas Oreach
Internal logic signal TRANSBL
Binary output: Delay 2
Setting: Echo
On = 1; Off = 0
Binary output: Meas Bward
Internal logic signal (TRIP2)
Bay protection functions REB500
1MRK 505 406-UEN B
GUID-994B7BE2-D432-4EA1-9F19-9D37D6B8F750 v1
Drain