Binary Outputs; Measurements; Function Settings; Parameters - ABB RELION REB500 Technical Manual

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 406-UEN B
5.15.3.3

Binary outputs

Pick-up
Tripping
5.15.3.4

Measurements

Current amplitude (only available if function trips)
5.15.4

Function settings

Table 101: Peak value over and undercurrent function - settings
Text
ParSet ç..1
Delay
I-Setting
f-min
NrOfPhases
CurrentInp
BlockInp
Trip
Start
5.15.5

Parameters

Table 102: Peak value over and undercurrent function - parameters
Signal
ParSet 4..1
Delay
I-Setting
f-min
MaxMin
NrOfPhases
CurrentInp
Table continues on next page
Bay protection functions REB500
Technical manual
Unit
Default
P1
s
0.01
I
4.0
N
Hz
40
1 Ph
CT-Addr
0
BinaryAddr
Always off
SignalAddr
SignalAddr
Description
Parameter for determining in which set of parameters a particular function is active.
Time between the function picking up and tripping.
Pick-up current setting.
Setting restrictions:
> 1.6 IN (when supplied from metering cores)
< 0.2 IN (when supplied from protection cores)
Defines the minimum frequency for which measurement is required.
Setting restriction:
< 40 Hz (when supplied from metering cores)
Defines operation as overcurrent or undercurrent.
Settings:
MAX: overcurrent
MIN: undercurrent
Defines whether single or three-phase measurement.
Defines the CT input channel.
All current inputs may be selected.
© Copyright 2019 ABB. All rights reserved
Bay protection functions
GUID-A1943FFD-B15A-4583-A19B-4352E7F6922C v1
GUID-8618F28F-F326-4B28-A986-23B529E2A35D v1
GUID-1C17972E-91CB-437B-9A6F-2DDC7F027B50 v1
Min
Max
(Select)
0.00
60.00
0.1
20
2
50
(Select)
GUID-BD1F3084-704F-4617-ABE3-D8B9C56574AD v1
Section 5
Step
0.01
0.1
1
183