Section 5
Bay protection functions
(ph-0 compensated)
Z
IEC19000416 V1 EN-US
Figure 15:
Measurement during processing period II
Processing period II commences after the first tripping signal or at the latest one period of the
system frequency after a starter picks up. The variables measured are the same as those
already processed during processing period I.
Only in the case of a cross-country fault in an ungrounded system or system with Petersen
coils is measurement restricted during processing period II to just the impedance loop
determined by the phase selection logic, otherwise all the phase-to-ground and phase-to-
60
START
U , U , U , U
L1
L2
L3
E
I , I , I , I
L1
L2
L3
E
Overcurrent
starter
N
Overcurrent
starter
Y
Loop =
phase selection
Z calculation
, Z
, (Z
),
Start
1-4
OR
Z
, direction
Back
N
Trip
Y
Signalling,
fault location,
Z(loop)
Stoping
the timers
Change to
processing
periode II
END
Processing period I
© Copyright 2019 ABB. All rights reserved
N
t > 1 periode
Y
Change to
processing
periode II
18000014-IEC19000416-1-en.vsdx
1MRK 505 406-UEN B
GUID-170FC07B-AEC8-4224-9871-EB915AC3D2FD v1
Bay protection functions REB500
Technical manual