1MRK 505 406-UEN B
I
0
I-Setting
I-dir
IEC19000466 V1 EN-US
Figure 62: Operation of a permissive directional comparison scheme
where:
•
<...>: optional function
•
Iasymm: asymmetrical currents under normal load conditions
•
I-dir: current enable for directional measurement (= 0.7 I-Setting)
•
I-Setting: current enabling level
•
MeasBwd: fault in backwards direction including Transient blocking
•
MeasBwd': fault in backwards direction
•
MeasFwd: fault in forwards direction
•
Rx: receive
•
T: trip
•
t TransBlk: blocking time
•
TB: transient blocking
•
t
Basic
•
t
Wait
•
Tx: send
•
V-setting: reference voltage
Blocking directional comparison scheme
Providing the conditions for directional measurement are fulfilled, that is, the current higher
I-dir and the voltage higher than its enabling level V-setting , a protection function
than
transmits a blocking signal to the remote station immediately when a fault is detected in the
backward direction.
A protection function measuring a fault in the direction of the protected line trips at the end of
the adjustable waiting time
Bay protection functions REB500
Technical manual
Tx: I-Setting MeasFwd t
T: I-Setting MeasFwd t
TB: MeasBwd t TransBlk
<Tx: MeasBwd Rx>
TB: MeasBwd t TransBlk
<Tx: MeasBwd Rx>
V-Setting
Basic functions
Echo and "Transient blocking"
Echo
: basic time
: waiting time
I-dir = 0.7 I-Setting
tWait , providing a blocking signal is not received beforehand.
© Copyright 2019 ABB. All rights reserved
Basic
Rx
Basic
I
asymm
U
0
18000061-IEC19000466-1-en.vsdx
Section 5
Bay protection functions
163