Section 5
Bay protection functions
5.6.3.3
Binary outputs
•
Pick-up
•
Tripping
5.6.3.4
Measurements
•
Voltage amplitude
5.6.4
Function settings
Table 78:
Text
ParSet 4..1
Delay
V-setting
MaxMin
NrOfPhases
VoltageInp
BlockInp
Trip
Start
5.6.5
Parameters
Table 79:
Signal
ParSet4..1
Delay
V-setting
MaxMin
NrOfPhases
VoltageInp
Table continues on next page
112
Definite time over- and undervoltage function - settings
Unit
s
U
N
AnalogAddr
BinaryAddr
SignalAddr
SignalAddr
Definite time over- and undervoltage function - parameters
Description
Parameter for determining in which set of parameters a particular function is active
Time delay between the function picking up and tripping
Voltage setting for tripping
Over- or undervoltage mode selection:
Settings:
•
MIN (3ph): Undervoltage. Three-phase functions detect the highest phase
voltage. Not permitted for single-phase functions.
•
MIN (1ph): Undervoltage. Three-phase functions detect the lowest phase
voltage.
•
MAX (3ph): Overvoltage. Three-phase functions detect the lowest phase
voltage. Not permitted for single-phase functions.
•
MAX (1ph): Overvoltage.Three-phase functions detect the highest phase
voltage.
Number of phases included in the measurement.
Analogue input channel
All the voltage channels are available for selection.
© Copyright 2019 ABB. All rights reserved
GUID-5275B141-2101-42B7-AD0D-978F0A957C8B v1
GUID-F4ACA098-AEAB-4E13-AB3C-962041125C10 v1
GUID-72811AEC-9706-47BE-8109-C03D393F0379 v1
Default
Min
Max
P1
(Select)
02.00
0.02
60.00
1.200
0.010
2.000
MAX (1ph)
(Select)
001
1
3
0
Always off
GUID-7D6408F1-C98B-4A4E-8DA6-0958CF9614AA v1
Bay protection functions REB500
1MRK 505 406-UEN B
Step
0.01
0.002
2
Technical manual