ABB RELION REB500 Technical Manual page 89

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 406-UEN B
Transmit logic
The task of the transmit logic is to boost (Com Boost) the PLC transmitter and transmit a
signal (signaling relay output Com Send) [HFSEND] to the opposite end of the line (signaling
relay output Com Boost) [HFBOOST].
General rules are:
The underreaching zone transmits the signal in a permissive underreaching transfer
tripping scheme (PUTT).
The overreaching zone transmits the signal in a permissive overreaching transfer tripping
scheme (POTT).
The reverse measuring zone transmits the blocking signal in an overreaching blocking
scheme (BLOCK OR).
PUTT_ON
POTT_ON
BLOCK_ON
PUTT_SEND
POTT_SEND
BLOCK_SEND
DISTBL
UWEAK_L1
UWEAK_L2
UWEAK_L3
START_L1L2L3
IEC19000437 V1 EN-US
Figure 33: TRANSBL segment
Table 63: Signals TRANSBL
Signal
PUTT_ON
POTT_ON
BLOCK_ON
PUTT_SEND
POTT_SEND
BLOCK_SEND
DISTBL
UWEAK_L1
UWEAK_L2
UWEAK_L3
START_L1L2T
Table continues on next page
Bay protection functions REB500
Technical manual
OR
OR
OR
AND
2000
In
Out
X
X
X
X
X
X
X
X
X
X
X
© Copyright 2019 ABB. All rights reserved
AND
AND
OR
18000032-IEC19000437-1-en.vsdx
Source
PUTT logic
POTT logic
BLOCK logic
PUTT logic
POTT logic
BLOCK logic
Enabling logic SUPBL
UL1 < Umin
UL2 < Umin
UL3 < Umin
Binary output: Start L1+L2+L3
Section 5
Bay protection functions
GUID-0CFA8B44-2841-4ADF-AB6D-891A6E04C55B v1
BIT_HF_ON
HF_SEND
HF_BOOST
Drain
83