Inputs And Outputs; Ct/Vt Inputs; Binary Inputs; Binary Outputs - ABB RELION REB500 Technical Manual

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 406-UEN B
Evaluation of instantaneous values (non-digitally filtered analogue signals) resulting in a
large permissible frequency range. Detection of the largest and smallest of the three-
phase voltages in the case of three-phase measurement.
No filtering of harmonics or DC component.
Choice of phase for the voltage inputs on busbar and line sides (for amplitude and phase-
angle adjustment).
Additional voltage input (for use in double busbar stations) with provision for remote
switchover.
Provision for remote selecting the operating mode.
5.7.3

Inputs and outputs

5.7.3.1

CT/VT inputs

Voltages (2 or 3 single or three-phase inputs) for:
5.7.3.2

Binary inputs

2 inputs for enabling the synchrocheck function (ReleaseInp1 and ReleaseInp2)
3 inputs for interlocking the synchrocheck O/Ps (BlckTrigBus1, BlckTrigBus2 and
BlckTrigLine)
1 input for bypassing the synchrocheck function (OverridSync)
2 inputs for remotely selecting operating mode (OpModeInp1 and OpModeInp2)
2 inputs for remotely switching voltage channels in double busbar stations (uBus1Activ
and uBus2Activ)
5.7.3.3

Binary outputs

Function pick-up (Start)
Circuit-breaker closing enable signal (PermitToClos)
Function disabled signal (SyncBlockd)
Enable output blocked signal (TrigBlockd)
Synchrocheck bypassed signal (OverridSync)
Amplitude difference in permissible range (AmplDifOK)
Phase-shift in permissible range (PhaseDifOK)
Frequency difference in permissible range (FreqDifOK)
Busbars energized (LiveBus)
Busbars de-energized (DeadBus)
Line energized (LiveLine)
Line de-energized (DeadLine)
Bay protection functions REB500
Technical manual
Busbar voltage — single-phase voltage measurement
Line voltage — single or three-phase voltage measurement
uBusInput1, uBusInput2 — single-phase
uLineInput — single or three-phase
© Copyright 2019 ABB. All rights reserved
Section 5
Bay protection functions
GUID-B6579214-65E0-4A16-8A18-2349524AA637 v1
GUID-15699343-8DDD-4FB4-A0A1-7DD8B563FD8F v1
GUID-83C56EC6-18F3-47A2-B316-731024859B8B v1
115