ABB RELION REB500 Technical Manual page 115

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 406-UEN B
Assuming a grading time of 0.5 s at 6 times the base current I
each of the relays is given by,
k
= 5 t
1
For operating times between 0.5 and 2.5 s, this results in the following settings for k
t [s]
0.5
1
1.5
2
2,5
The characteristics according to BS 142 are set as follows:
normal inverse:
very inverse:
extremely inverse:
long time earth fault:
Characteristic angle
Determining the phase-angle of the current provides an additional criterion for preserving
discrimination compared with non-directional overcurrent protection. The directional
sensitivity is ±180° in relation to the reference voltage. This is illustrated in the following
diagram.
Bay protection functions REB500
Technical manual
k
[s]
1
2.5
5
7.5
10
12.5
k
= 0.14 s
1
k
= 13.5 s
1
k
= 80 s
1
k
= 120 s
1
© Copyright 2019 ABB. All rights reserved
Bay protection functions
is required, the factor k
B
1
Section 5
for
1
:
109