Fusing data

EN 60204-1
Inverters
i550-C3.0/400-3
i550-C4.0/400-3
i550-C5.5/400-3
i550-C7.5/400-3
i550-C11/400-3
i550-C15/400-3
i550-C18/400-3
i550-C22/400-3
i550-C30/400-3
i550-C37/400-3
i550-C45/400-3
i550-C55/400-3
i550-C75/400-3
i550-C90/400-3
i550-C110/400-3
The connection data according to UL can be found
Please note that from 15 kW onwards a mains choke must always be used.
Fuse
Characteristics
Max. rated
current
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gR
gR
gR
gR
under:4Connection according to UL
3-phase mains connection 400 V "Light Duty"
Circuit breaker
Characteristics
Max. rated
A
25
B
25
B
25
B
32
B
32
B
63
B
63
B
63
B
80
B
100
B
125
B
160
-
160
-
300
-
300
-
Technical data
Fusing data
Earth-leakage circuit
breaker
current
A
25
≥ 30 mA, type B
25
≥ 30 mA, type B
25
≥ 300 mA, type B
32
≥ 300 mA, type B
32
≥ 300 mA, type B
63
≥ 300 mA, type B
63
≥ 300 mA, type B
63
≥ 300 mA, type B
80
≥ 300 mA, type B
100
≥ 300 mA, type B
125
≥ 300 mA, type B
-
≥ 300 mA, type B
-
≥ 300 mA, type B
-
≥ 300 mA, type B
-
≥ 300 mA, type B
^ 50
117