3-Phase Mains Connection 230/240 V - Lenze i550-C0.25/120-1 Project Planning Manual

Cabinet 0.25...132 kw
Hide thumbs Also See for i550-C0.25/120-1:
Table of Contents

Advertisement

3-phase mains connection 230/240 V

The connection plan is valid for the inverters i550-Cxxx/230-3.
The inverters i550-Cxxx/230-3 do not have an integrated RFI filter in the AC
mains supply.
In order to meet the EMC requirements according to EN 61800−3, an external
EMC filter according to IEC EN 60939 must be used.
The user must verify that the conformity with EN 61800−3 is fulfilled.
L1
L2
L3
N
PE
F1
...
F3
3/ PE
Q1
AC
170 V ... 264 V
45 Hz ... 65 Hz
+
+
"
J
J
M
+
3~
Fig. 5: Wiring example
S1
Start/Stop
Fx
Fuses
CANopen
Modbus RTU
AC 240 V
3 A
+24 V
100 mA
"
DC
24 V
(+19.2 ... +28.8 V)
Q1
---
Information on electrical installation
3-phase mains connection 230/240 V
PROFIBUS
EtherCAT
PROFINET
EtherNet/IP
Application I/O
Standard I/O
+10 V
SELV PELV
/
DI3
S1
Mains contactor
Dashed line = options
Mains connection
3/N/ PE
AC
208 V ... 240 V
Modbus TCP
POWERLINK
IO-Link
"
DI4
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents