Motor Connection - Lenze i550-C0.25/120-1 Project Planning Manual

Cabinet 0.25...132 kw
Hide thumbs Also See for i550-C0.25/120-1:
Table of Contents

Advertisement

Motor connection

Switching in the motor cable
Switching on the motor side of the inverter is permissible:
For safety shutdown (emergency stop).
In case several motors are driven by one inverter (only in V/f operating mode).
Please note the following:
The switching elements on the motor side must be dimensioned for with the
maximum occurring load.
Motor cable lengths
The rated data for the motor cable length must be observed.
Keep the motor cable as short as possible as this has a positive effect on the drive
behaviour and the EMC.
Several motors connected to an inverter form a group drive. In case of group drives, the
resulting motor cable length l
l
[m] = (l
+ l
+ l
... l
) ∙ √i
res
1
2
3
i
l
Resulting length of the motor cables
res
l
Length of the single motor cable
x
i
Number of the single motor cables
is relevant:
res
Information on electrical installation
Motor connection
61