Fusing Data - Lenze i550-C0.25/120-1 Project Planning Manual

Cabinet 0.25...132 kw
Hide thumbs Also See for i550-C0.25/120-1:
Table of Contents

Advertisement

Technical data
3-phase mains connection 400 V

Fusing data

Fusing data
EN 60204-1
Inverters
i550-C0.37/400-3
i550-C0.55/400-3
i550-C0.75/400-3
i550-C1.1/400-3
i550-C1.5/400-3
i550-C2.2/400-3
i550-C3.0/400-3
i550-C4.0/400-3
i550-C5.5/400-3
i550-C7.5/400-3
i550-C11/400-3
i550-C15/400-3
i550-C18/400-3
i550-C22/400-3
i550-C30/400-3
i550-C37/400-3
i550-C45/400-3
i550-C55/400-3
i550-C75/400-3
i550-C90/400-3
i550-C110/400-3
The connection data according to UL can be found
Please note that from 22 kW onwards a mains choke must always be used.
106
Fuse
Characteristics
Max. rated
current
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gG/gL or gRL
gR
gR
gR
gR
under:4Connection according to UL
Circuit breaker
Characteristics
Max. rated
A
10
B
10
B
10
B
16
B
16
B
16
B
25
B
25
B
25
B
32
B
32
B
63
B
63
B
63
B
80
B
100
B
125
B
160
-
160
-
300
-
300
-
Earth-leakage circuit
breaker
current
A
10
≥ 30 mA, type B
10
≥ 30 mA, type B
10
≥ 30 mA, type B
16
≥ 30 mA, type B
16
≥ 30 mA, type B
16
≥ 30 mA, type B
25
≥ 30 mA, type B
25
≥ 30 mA, type B
25
≥ 300 mA, type B
32
≥ 300 mA, type B
32
≥ 300 mA, type B
63
≥ 300 mA, type B
63
≥ 300 mA, type B
63
≥ 300 mA, type B
80
≥ 300 mA, type B
100
≥ 300 mA, type B
125
≥ 300 mA, type B
-
≥ 300 mA, type B
-
≥ 300 mA, type B
-
≥ 300 mA, type B
-
≥ 300 mA, type B
^ 50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents