5 COMMISSIONING

5.1 Preliminary checks

First ignition must be performed by a qualified
competent engineer.
Before starting the boiler, check:
- That supply networks (electricity, water, gas) correspond
to the data
- That the flue pipes and air suction pipes are installed correctly
- that spacing conditions for regular maintenance are
guaranteed if the boiler is placed inside or between items
of furniture
- The Gas system is sound
- That the fuel flow rate corresponds to values required by the
boiler
- That the fuel supply system is sized to provide the correct
low rate to the boiler, and that it has all the safety and
control devices required
-
That the circulator rotates freely because, occasionally
from new or after a long period of dormancy the impeller
can stick.
See below
Releasing of the circulating pump shaft
- Insert a screwdriver in hole (1) of the circulator.
- Press (a) and turn with Phillips screwdriver (b) to release
the pump shaft
Perform this operation with caution to avoid damaging components.
14
a
1
b
5.2 Initial Programming
At start up the control displays an initial screen
showing the firmware version.
Pressing "ok" a guided procedure is started for configuring
the system; select the desired options with the "up" and
"down" keys, confirming the selections made:
Set the TIME and DATE confirming each parameter by
pressing ok to confirm
Select MASTER from the next screen and ok to confirm
SLAVE
MASTER
When this screen is presented select FROM AKM and
confirm OK