Each time that the boiler is powered an automatic venting
cycle is carried out lasting 2 min. To interrupt the vent
cycle, carry out the procedure explained in the section
"5.3 First commissioning".
- Set the boiler to OFF
.
menu and then BOILER
FRI
18/05/2013
MENU
42
INFO
HOT WATER TEMPERATURE
CUSTOMISATION
Configuring the boiler to suit the system
Through the control it is possible to access using
the TECHNICAL menu a series of parameters
that can be programmed allowing you to
personalize the operation of this appliance based
on the type of system to which it is attached.
set parameters according to the desired operating mode
In all cases at least step 5.2.1 must be followed
Typical Boiler configuration
5.2.1
- Access the technical parameters as explained in the section "4.1 Access
to the technical parameters".
- With the "up" and "down" keys select PARAMETERS, confirming the
selection.
- Select from among the following options with the "up" and "down",
keys, confirming the selection.
from REC10 selecting the STATE
PLANT
12:17
1.3 bar
STATE
°C
SET
TIMER OFF CH
RESET TIMERS CH
DHW THERMOSTAT
INSTALLER
- TIMER OFF CH
This parameter allows you to change the TIMER OFF CH, regarding
the delay time introduced for re-igniting the burner in the face of an off
due to the heating temperature being reached. The factory setting for
this parameter is 3 minutes and can be set to a value between 0 min
and 20 min selecting as desired with the "up" and "down", keys
confirming the selection.
TIMER OFF CH
- RESET TIMERS CH
This parameter allows you to reset the REDUCED HEATING MAXIMUM
OUTPUT TIMING, during which the speed of the fan is limited to 75%
of the maximum heating output that has been set, and the TIMER OFF
CH. The factory setting for this parameter is FUNCTION NON ACTIVE,
select FUNCTION ACTIVE using the keys "up" and "down", confirming
the selection for resetting the timings.
RESET TIMERS CH
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
INSTALLER
- DOMESTIC HOT WATER THERMOSTAT
This parameter allows you to set the type of DOMESTIC HOT WATER
THERMOSTAT.
The factory setting for this parameter is RELATED, i.e. for domestic hot
water the boiler switches off at set point +5°C and restarts at set point
+4°C.
To select the ABSOLUTE values, where the boiler for domestic hot water
will still switch off at 65°C and restart at 63°C, use the keys "up" and
"down".
DHW THERMOSTAT
INSTALLER
PREHEATING
3
MIN
RELATED
ABSOLUTE
ENGLISH
15