Appendix A: VVT Zone II Points/Properties
Point Name/Description
Test and Balance – Use the following command buttons when commissioning a zone, balancing the system (page
42), replacing the zone controller, or troubleshooting. If Automatic Control is not selected within 4 hours, the
controller will resume normal control.
Calibrated Damper Close – Forces the damper closed so the 0% damper position can be set.
Calibrated Damper Open – Forces the damper to its maximum open position so that the 100% damper position can
be set.
Cool Max – Forces the damper to its cool maximum position regardless of its current local mode.
Cool Min – Forces the damper to its cool minimum position regardless of its current local mode.
Automatic Control – Returns the damper to its normal control routines. This must be activated when you finish
using any of the other Test and Balance commands.
Damper Full Close – Overrides the damper to its full closed position.
Heat Max – Forces the damper to its heat maximum position regardless of its current local mode.
Heat Min – Forces the damper to its heat minimum position regardless of its current local mode.
Reheat Min – Forces the damper to its reheat position regardless of its current local position.
Vent – Forces the damper to its ventilation position regardless of its current local mode.
Sensor Binder / Zone Temp / Zone Humidity / ZS Zone CO2
Ctrl+click on the name of these properties to access the microblock popup Properties
page > Details tab. See below for instructions on configuring your ZS or wireless sensors.
See the microblock Help for more detailed explanations.
Sensor Binder - Use the Associated Sensors table to configure the Rnet to use additional
ZS or wireless sensors.
Network Type - Set to Rnet
Address - Enter the DIP switch settings that are on the additional ZS sensors (up to 5
total) or RnetID assigned to each wireless sensor in SensorBuilder
Lock Display - Check to make the sensor display-only
VVT Zone II Controller
Installation and Start-up Guide
80
Default/Range
D:
(Index) - (1)
Network Type - Rnet
Address - 1
CARRIER CORPORATION ©2019
All rights reserved