Installing the VVT Zone II
Linked actuators
You can wire up to 4 of the following Belimo actuators to the VVT Zone II's analog output. Use like actuators so
that travel times and other parameters coincide.
LMX24-MFT P-10028
NMX24-MFT P-10028
AMX24-MFT P-10028
1
Install the actuators according to the manufacturer's instructions.
2
Wire the actuators to the controller using the diagram below.
3
Set the direction rotation switch on each actuator to CW.
VVT Zone II Controller
Installation and Start-up Guide
45 in.-lb (5 Nm) actuator with 0–10 Vdc control
90 in.-lb (10 Nm) actuator with 0–10 Vdc control
180 in.-lb (20 Nm) actuator with 0–10 Vdc control
38