VVT Zone II Controller
Installation and Start-up Guide
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal.
The power, network, input, and output connections are also protected against
transient excess voltage/surge events lasting no more than 10 msec.
CAUTION To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
You attach a BT485 (not included) to a controller at the beginning and end of a
network segment to add bias and to terminate a network segment.
LEDs indicate status of communications, running, errors, power, and digital
outputs
32 to 130°F (0 to 54.4°C), 10–90% relative humidity, non-condensing
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
UL94-5VA plenum rated enclosure for installation in plenum (or other space for
environmental air) in accordance with NEC Section 300.22 (c) and (d)
Width:
8.9 in. (22.7 cm)
Height:
5.9 in. (15.0 cm)
7.1 in. (18.0 cm) from left side controller mounting hole centerline to actuator
mounting hole centerline
Width:
6.4 in. (16.3 cm)
Height:
5.7 in. (14.5 cm)
2.1 in. (5.3 cm)
Depth:
5.3 in. (13.4 cm) from left side controller mounting hole centerline to right side
controller mounting hole centerline
Width:
3.0 in. (7.6 cm)
Height:
5.9 in. (15.0 cm)
Depth:
2.5 in. (6.4 cm)
4.4 in. (11.2 cm) from shaft centerline to actuator mounting hole centerline
2.5 in. (6.4 cm) minimum
Minimum shaft diameter: .25 in. (.64 cm)
Maximum shaft diameter: .63 in. (1.59 cm)
Minimum shaft length: 1.75 in. (4.45 cm)
1.8 lbs (0.82 kg)
Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L,
Protocol Revision 9
UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B, Class B, CE
4
CARRIER CORPORATION ©2019