Carrier VVT Zone II Installation And Startup Manual page 26

Table of Contents

Advertisement

Installing the VVT Zone II
Wiring diagram for #33ZCSPTCO2:
#33ZCT55CO2
1
Wire the sensor to the controller. See appropriate diagram below.
2
Install a field supplied 250 Ohm 1/4 watt 2% tolerance resistor across the controller's RH/CO2 and Gnd
terminals.
3
Verify that the RH/CO2 jumper is set to 0-5Vdc on the VVT Zone II.
VVT Zone II Controller
Installation and Start-up Guide
22
CARRIER CORPORATION ©2019
All rights reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vvt zone

Table of Contents