Appendix D: BACnet points list
Point Name
Cool Min Damper Position
System Space Temperature
Airside Linkage Status
DCV Control
Fan
Heat Enable
Occupancy Status
Reset Filter Alarm
RH Control
Setpoint Adjustment
Shutdown
Air Source Mode
BAS On / Off
Optimal Start Type
Space Temp Source
Terminal Mode
Terminal Type
VVT Zone II Controller
Installation and Start-up Guide
Point
Units
Access
R
%
R/W
°F
0=Not Active
R
1=Active
R/W
0=Disable
1=Enable
R
0=Off
1=On
R/W
0=Disable
1=Enable
0=Unoccupied
R
1=Occupied
R/W
0=Off
1=On
R/W
0=Disable
1=Enable
R/W
0=Disable
1=Enable
0=Inactive
R/W
1=Active
R
1=Off
2=Warmup
3=Heat
4=Cool
5=Freecool
6=Pressure
7=Evac
8=Vent
R/W
1=Inactive
2=Occupied
3=Unoccupied
R/W
1=None
2=Temp
Compensated
3=Learning Adaptive
R
1=Sensor Failure
2=SPT Sensor
3=T55 / T56
4=Network
5=Airside Linkage
6=Locked Value
7=ZS Sensor
8=Wireless Sensor
R
1=Off
2=Heating
3=Warm-Up
4=Vent
5=N/A
6=Cooling
7=Dehumidify
8=Reheat
9=Pressurize
10=Evacuate
11=Shutdown
12=IAQ Override
13=Air Balancing
1=Single Duct
R
2=Parallel Fan
3=Series Fan
96
Default Value
BACnet Point Name
cl_min_dmp_pos
-999
system_spt
a_link_status
Inactive (0)
dcv_enable
sfan_status
Active (1)
ht_enable
occ_status
Inactive (0)
filter_rntm_clr
Inactive (0)
rh_enable
Active (1)
stpt_adj_enable
Inactive (0)
shutdown
link_ahu_mode
1
keypad_ovrde
2
start_type
spt_status
terminal_status
terminal_type
BACnet
BACnet Object ID
AV:1902
BV:2601
BV:1003
BV:1012
BV:2008
BV:7517
BV:1013
BV:9001
MSV:2005
MSV:1001
MSV:2009
MSV:2003
MSV:2006
MSV:2007
CARRIER CORPORATION ©2019
All rights reserved