Point Name
Cool Min Damper Position
Zone Type
Airside Linkage Status
Filter
High SPT
Indoor Air Quality
Low SPT
Network OAT
Space Relative Humidity
Space Temp Sensor
Supply Air Temperature
Wireless Battery Strength Alarm
Wireless Signal Strength Alarm
ZS/WS Sensor Configuration
VVT Zone II Controller
Installation and Start-up Guide
Point
Units
Access
R
%
R
1=Slave
2=VVT Master
3=VAV Master
R
0=Normal
1=Alarm
R
0=Clean
1=Dirty
R
0=Normal
1=Alarm
R
0=Normal
1=Alarm
R
0=Normal
1=Alarm
R
0=Normal
1=Alarm
R
0=Normal
1=Alarm
R
0=Normal
1=Alarm
R
0=Normal
1=Alarm
0=Normal
R
1=Alarm
R
0=Normal
1=Alarm
R
0=Normal
1=Alarm
97
Default Value
BACnet Point Name
cl_min_dmp_pos
zone_type
air_linkage_fail
filter_alarm
spt_hi_alarm
iaq_alarm
spt_lo_alarm
oat_fail
sprh_hi_alarm
spt_fail
sat_alarm
ws_batt_alarm
ws_sig_alarm
zs_config_fail
Appendix D: BACnet points list
BACnet
BACnet Object ID
MSV:2008
BV:7030
BV:7017
BV:7011
BV:7005
BV:7012
BV:7029
BV:7018
BV:7001
BV:7004
BV:7064
BV:7065
BV:7055
CARRIER CORPORATION ©2019