Appendix A: VVT Zone II Points/Properties
Point Name/Description
Effective Cool Setpoint – The current cooling setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from Optimal Start to Demand
Limit.
Relative Humidity Source – The source of the relative humidity value.
IAQ Source – The source of the indoor air quality value.
Outdoor Air Temperature Source – The source of the outdoor air temperature.
Remaining Heat Delay – If Heat Delay is Active, this is the remaining delay time.
Cooling Demand Level – The system cool demand level received over the network.
Heating Demand Level – The system heat demand level received over the network.
Heat Delay – The status of the terminal heat delay.
Remaining Heat Delay – If Heat Delay is Active, this is the remaining delay time.
Calculated DCV Damper Position – If the controller is in IAQ Override mode, this is the
calculated minimum damper position that will be maintained to satisfy the mode.
Calculated Dehumidify Dmpr Position – If the controller is in Dehumidify mode, this is
the calculated minimum damper position that will be maintained to satisfy the mode.
Reset Filter Alarm – Set this to On to reset an active Filter Alarm and restart the Filter
Service Alarm Timer. After the alarm returns to normal, this automatically changes to
Off.
Occupancy Contact State - The physical state of the Remote input.
Cooling BTU's – Current Cooling Energy being delivered to the space.
Heating BTU's – Current Heating Energy being delivered to the space.
Occupancy
VVT Zone II Controller
Installation and Start-up Guide
84
Default/Range
R:
_°F/C
R:
N/A
Local
Network
Linkage
Locked Value
ZS Sensor
R:
N/A
Local
Network
Linkage
Locked Value
ZS Sensor
R:
N/A
Local
Network
Linkage
Locked Value
R:
0 to 60 minutes
R:
0 to 3
R:
0 to 3
R:
Inactive/Active
R:
0 to 60 minutes
R:
0 to 100%
R:
0 to 100%
D:
Off
R:
On/Off
R:
Open/Closed
R:
0 to 99999 BTU
(0 to 99999 KJoules)
R:
0 to 99999 BTU
(0 to 99999 KJoules)