Start-Up; Configuring The Vvt Zone Ii's Properties - Carrier VVT Zone II Installation And Startup Manual

Table of Contents

Advertisement

Start-up

Start-up
Use one of the following interfaces to start up, access information, read sensor values, and test the controller.
This interface...
Field Assistant application -
Runs on a laptop that connects to controller's Local Access port
Equipment Touch device -
Connects to controller's Rnet port
i-Vu® application
Available for BACnet systems only
System Touch device
Available only for BACnet MS/TP systems.
Wire to a BACnet MS/TP network connector and a 24 Vac power supply
1
Requires a USB Link (Part #USB-L).
2
See the Equipment Touch Installation and Setup Guide for detailed instructions.
3
See the System Touch Installation and Setup Guide for detailed instructions.
CAUTION If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.

Configuring the VVT Zone II's properties

To start up the VVT Zone II, you must configure certain points and properties. Appendix A (page 65) is a complete
list of all the points and properties, with descriptions, defaults, and ranges. These properties affect the unit
operation and/or control. Review and understand the meaning and purpose of each property before changing it.
Unit Configuration properties (page 66)
Setpoint Configuration properties (page 68)
Service Configuration properties (page 77)
Linkage properties (page 87)
See Appendix A (page 65) for a complete list of the controller's points/properties.
NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.
VVT Zone II Controller
Installation and Start-up Guide
2
40
Provides a...
Temporary interface
1
Temporary or permanent
interface
Permanent interface
Temporary or permanent
interface
3
CARRIER CORPORATION ©2019
All rights reserved