Settings For The "Analog Output" Function (Analog Output Menu) - ProMinent Sigma/ 2 Control S2Cb Operating Instructions Manual

Diaphragm motor-driven metering pump
Table of Contents

Advertisement

Setting

8.6.6 Settings for the "Analog output" function (ANALOG OUTPUT menu)

Main menu
Mode
Settings
Service
Information
Language
Continuous
display
„Strokes / min"
To
„Capacity"
To
To
„Capacity at 20 mA"
58
Settings
Analog
Auxiliary freq.
Calibrate
Dosing
Analog output
Using the "Analog output" programmable function, you can match the
pump current output signal (optional) to your requirements.
The signal I of the current output signal one of the three following varia‐
bles:
Strokes/min
n
Capacity
n
Capacity at 20 mA
n
In the "Stop" or "Pause" states (either because of a fault or operation) or
"Pause" the current output transmits a current of 4 mA or 0 mA.
The pump calculates the signal for
lowing formula (here for the range 4...20 mA):
I(4...20) = 16 x (f/fmax) + 4
with
l
- Output current in mA
f
- Stroke rate in strokes/min
fmax - Maximum stroke rate in strokes/min
„Contact" and „Batch" operating modes, f is the stroke rate which is
In the
set in the "Stroke rate" continuous display.
The pump calculates the signal for
formula (here for the range 4...20 mA):
I(4...20) = 16 x (f/f
with
l
- Output current in mA
f
- Stroke rate in strokes/min
H
- Stroke length in %
f
- Maximum stroke rate in strokes/min
max
„Contact" and „Batch" operating modes, f is the stroke rate which is
In the
set in the "Stroke rate" continuous display.
This menu item is only available with a calibrated pump.
The pump calculates the signal for
following formula (here for the range 4...20 mA):
I(4...20) = 16 x(L/L
with
Analog output
Range
Function
End
„Strokes / min" according to the fol‐
„Capacity" according to the following
) x (H/100) + 4
max
„Capacity at 20 mA" according to the
) + 4
max
Range
0..20mA
4..20mA
Function
Strokes / min
Capacity
Capacity at 20mA