Settings For The "Dosing Monitor" Function (Dosing Monitor Menu) - ProMinent Sigma/ 2 Control S2Cb Operating Instructions Manual

Diaphragm motor-driven metering pump
Table of Contents

Advertisement

Setting

8.6.4 Settings for the "Dosing monitor" function (DOSING MONITOR menu)

Main menu
Mode
Settings
Service
Information
Language
Continuous
display
56
Settings
Analog
Auxiliary freq.
Calibrate
Dosing monitor
Relay
„Dosing monitor" only appears if a dosing monitor is connected
The menu
to the "dosing monitor" terminal. The dosing monitor records the individual
pressure surges of the pump at the pressure connector during pulsed
metering and reports them back to the pump. In the event that this feed‐
back message remains missing in a sequence as often as set in the menu
„Dosing monitor" under „Tolerance" (due to a failure or too low a
metering level), then this function stops the pump.
The last menu option
case should lead to an
„Dosing monitor" can be deactivated under „Control" .
The function
„Auxiliaryfreq." (auxiliary frequency) operating mode, the function
For
„Metering monitor" can be disabled.
If the "Flow Control" metering monitor is not running
cleanly due to the flow being too low and pressure
surges by the feed chemical, we would advise checking
the use of our ultrasound flow meter Dulco Flow
08.
Dosing
control
Tolerance
at auxiliary
Signalization
End
„Signalization" provides the choice, of whether this
„Error" or a „Warning" .
control
Off
On
Tolerance
0 0 1 0
at auxiliary
Off
On
Signalization
Off
On
®
DFMa