Table A- 7 Input/Output Wiring (Tb4) - 7Me39400Al03 And 7Me39400Al04 Expanded I/O Module - Siemens SITRANS FUH1010 Product Instruction Manual

Liquid ultrasonic flowmeter / interface detector (ifd)
Hide thumbs Also See for SITRANS FUH1010:
Table of Contents

Advertisement

Note
Relays shown in Power OFF position, which is the same as the alarm assertion position.
*7ME39400AL03 Mercury Relay only available with Normally Open.
Table A- 7
Input/Output Wiring (TB4) - 7ME39400AL03 and 7ME39400AL04 Expanded I/O Module
Pin #
Signal
Definition
1
AUX
Isolated Loop
I01+
Supply Io1
2
AUX
Io1 4-20 mA
I01-
Output
3
AUX
Isolated Loop
I02+
Supply Io2
4
AUX
Io2 4-20 mA
I02-
Output
5
AUX
Isolated Loop
I03+
Supply Io3
6
AUX
Io3 4-20 mA
I03-
Output
7
AUX
Isolated Loop
I04+
Supply Io4
8
AUX
Io4 4-20 mA
I04-
Output
Note
Auxiliary 4-20mA loops are assigned and spanned under menu control of Vo and PGEN
outputs.
FUH1010 IP65 NEMA 4X Precision Volume
Operating Instructions, 01/2013, A5E32122003-AA
Description
Single CH
Function
Io1 External
+30gV max. supply voltage allowed
Power
Io1 Signal
Same output assignment as TB2-9
Io2 External
+30V max. supply voltage allowed
Power
Io2 Signal
Same output assignment as TB2-11
Io3 External
System outputs assignable and
Power
scalable to flow related parameters.
4-20mA outputs also provide a fault
Io3 Signal
indication by dropping to 2mA if
assigned to flow rate and under fault
Io4 External
conditions.
Power
Io4 Signal
A.2 I/O Connections and Wiring
Dual CH
Dual Path
Function
Function
Appendix A
Dual Path
Quad Path Only
Only
Function
Function
Not Used
+30 V max. Same as TB2-1
+30 V max. Same as TB2-3
171