Process Data - Danfoss FC 300 Profibus Manual

Table of Contents

Advertisement

FC 300 Profibus

Process Data

Use the process data part of the PPO for controlling and monitoring the FC 300 via the PROFIBUS.
Process Control Data
Process data sent from the PLC to the FC 300 is
defined as Process Control Data (PCD).
PCD 1 contains a 16-bit control word, where each bit controls a specific function of the FC 300, see section
Control Profile. PCD 2 contains a 16-bit speed set point in percentage format. The value is transmitted in
integers (0-32767). The value 16384 (4000 Hex) corresponds to 100%. Negative numbers are formed
with the aid of the twos complement.
The bus reference value has the following format:
Par. 3-00 Reference range = [0]:
Par. 3-00 Reference range = [1]:
where the value 4000h represents 100% speed of the FC 300.
The content of PCD 3 to PCD 10 is programmed in par. 9-15 PCD write configuration and par. 9-16 PCD
read configuration.
Process Status Data
Process data sent from the FC 300 contains
information about the current state of the FC 300.
PCD 1 contains a 16-bit status word, where each bit contains information regarding a possible state of
the FC 300.
PCD 2 contains the value of the current speed of the FC 300 in percentage format.
The value is transmitted in integers (0-32767). The value 16384 (4000 Hex) corresponds to 100%.
Negative numbers are formed with the aid of the twos complement.
The content of PCD 3 to PCD 10 is programmed in par. 9-16 PCD read configuration.
How to Control the FC 300
refMIN → refMAX (0 - 100%)
0-16384 (0 - 4000 Hex)
-refMAX → + refMAX ( -100 → + 100%)
-16384 → + 16384 (8000 → 4000 Hex)
MG.33.C2.02 - VLT is a registered Danfoss trademark
Master →
slave
1
2
3
......
CTW MRV PCD ...... PCD
PCD read/write
Slave →
master
1
2
3
......
STW MAV PCD ...... PCD
PCD read/write
10
10
27