FC 300 Profibus
8-55 Set-up Select
Option:
Digital input
Bus
Logic AND
*
Logic OR
Function:
Choose between controlling the drive via the
terminals (digital input) and/or via the bus.
If you select Bus, you can only activate Selection
of Setup if it is transmitted via the serial
communication port or fieldbus option. If you select
Logic AND, you must also activate the command via
one of the digital inputs. If you select Logic OR,
you can also activate the Set-up command via one
of the digital inputs.
NB!:
This parameter is active only when par.
8-01 Control Site is set to [0] Digital and
control word.
8-56 Preset Reference Select
Option:
Digital input
Bus
Logic AND
*
Logic OR
Function:
Choose between controlling the drive via the
terminals (digital input) and/or via the bus.
If you select Bus, you can only activate the Preset
Reference command if it is transmitted via the serial
communication port or fieldbus option. If you select
Logic AND, you must also activate the command via
one of the digital inputs. If you select Logic OR, you
can also activate the Preset Reference command via
one of the digital inputs.
NB!:
This parameter is active only when par.
8-01 Control Site is set to [0] Digital and
control word.
8-90 Bus Jog 1 Speed
Range:
0. - par. 4-13 RPM
Function:
Sets a fixed speed (jog) activated via the serial port
or bus option.
60
Parameters
[0]
[1]
[2]
Sets a fixed speed (jog) is activated via the serial
[3]
port or bus option
[0]
[1]
[2]
[3]
*
100.
RPM
MG.33.C2.02 - VLT is a registered Danfoss trademark
8-91 Bus Jog 2 Speed
Range:
0. - par. 4-13 RPM
Function:
*
200.
RPM