Danfoss FC 300 Profibus Manual page 64

Table of Contents

Advertisement

FC 300 Profibus
Function:
Delivers the Status word for a Master Class 2 in the
same format as PCD 2. The value of this parameter
is only valid if the control priority is set to Master
Class 2. This parameter is only visible for Profibus
Master Class 2, not for Master Class 1, standard
bus, or LCP.
9-70 Edit Set-up
Option:
Factory Set-up
Set-up 1
Set-up 2
Set-up 3
Set-up 4
*Active set-up
Function:
Choose the set-up in which programming (change
of data) will be performing during operation.
It is possible to programme the 4 set-ups
independently of the set-up selected as active.
Parameter access from each master will be directed
to the set-up which has been selected by the
individual master (cyclic, acylic MCL1, first acyclic
MCL2, second acyclic MCL2, third acyclic MCL2).
See section Parameter Access in General.
9-71 Profibus Save Data Values
Option:
*
Off
Store edit setup
Store all set-ups
Function:
Parameter values changed via Profibus are not
automatically stored into non-volatile memory. Use
this parameter to activate a function that stores all
parameter values in the EEPROM. Thus, you retain
changed parameter values at power-down.
- [0] Off: The store function is inactive.
- [1] Store edit set-up: All parameter values in
the set-up selected in par. 9-70 are stored in the
EEPROM.
The value returns to [0] Off when all values are
stored.
-[2] Store all set-ups: All parameter values for all
set-ups are stored in the EEPROM. The value returns
to [0] Off when all parameter values are stored.
9-72 ProfibusDriveReset
Option:
*
No action
Comm. option reset
64
Parameters
Resets the drive (as for power-cycle). The drive
disappears from the bus, which might cause a
communication error from the master.
[0]
[1]
[2]
[3]
[4]
Holds a list of all the defined drive parameters
[9]
available for Profibus.
Holds a list of all the defined drive parameters
available for Profibus.
[0]
[1]
[2]
Holds a list of all the defined drive parameters
available for Profibus.
Holds a list of all the defined drive parameters
[0]
available for Profibus.
[3]
MG.33.C2.02 - VLT is a registered Danfoss trademark
Function:
9-80 Defined Parameters (1)
Array [116]
Option:
No LCP access
Read only
0 - 115
Function:
9-81 Defined Parameters (2)
Array [116]
Option:
No LCP access
Read only
0 - 115
Function:
9-82 Defined Parameters (3)
Array [116]
Option:
No LCP access
Read only
0 - 115
Function:
9-83 Defined Parameters (4)
Array [116]
Option:
No LCP access
Read only
0 - 115
Function:
*
0
*
0
*
0
*
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents