Control Profile; Profidrive Control Profile - Danfoss FC 300 Profibus Manual

Table of Contents

Advertisement

FC 300 Profibus

Control Profile

The FC 300 can be controlled according to the PROFIdrive profile, or the Danfoss FC profile. Select the desired
control profile in par. 8-10 Control word profile. The choice of profile affects the control and status word only.
The PROFIdrive control profile and Danfoss FC control profile sections provide a detailed description of
control and status data.

PROFIdrive Control Profile

This section describes the functionality of the control word and status word in the PROFIdrive profile. Select
this profile by setting par. 8-10 Control word profile to PROFIdrive.
Control Word according to PROFIdrive Profile
(CTW)
The Control word is used to send commands from
a master (e.g. a PC) to a slave.
Explanation of the Control Bits
Bit 00, OFF 1/ON 1
Normal ramp stop using the ramp times of the actual selected ramp.
Bit 00 = "0" leads to the stop and activation of the output relay 1 or 2 if the output frequency is 0 Hz and if
[Relay 123] has been selected in par. 5-40 Function relay.
When bit 00 = "1", the frequency converter is in State 1: "Switching on inhibited".
Please refer to the PROFIdrive State Transition Diagram, at the end of this section.
Bit 01, OFF 2/ON 2
Coasting stop
When bit 01 = "0", a coasting stop and activation of the output relay 1 or 2 occurs if the output frequency is
0 Hz and if [Relay 123] has been selected in par. 5-40 Function relay.
When bit 01 = "1", the frequency converter is in State 1: "Switching on inhibited". Please refer to the
PROFIdrive State Transition Diagram, at the end of this section.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of par. 3-81 Quick stop ramp time. When bit 02 = "0", a quick stop and
activation of the output relay 1 or 2 occurs if the output frequency is 0 Hz and if [Relay 123] has been
selected in par. 5-40 Function relay.
When bit 02 = "1", the frequency converter is in State 1: "Switching on inhibited".
Please refer to the PROFIdrive State Transition Diagram, at the end of this section.
How to Control the FC 300
MG.33.C2.02 - VLT is a registered Danfoss trademark
Bit
Bit = 0
00
OFF 1
01
OFF 2
02
OFF 3
03
Coasting
04
Quick stop
05
Hold frequency
output
06
Ramp stop
07
No function
08
Jog 1 OFF
09
Jog 2 OFF
10
Data invalid
11
No function
12
No function
13
Parameter set-up
14
Parameter set-up
15
No function
Bit = 1
ON 1
ON 2
ON 3
No coasting
Ramp
Use ramp
Start
Reset
Jog 1 ON
Jog 2 ON
Data valid
Slow down
Catch up
Selection lsb
Selection msb
Reverse
29