Fault Messages Via Dp Diagnosis - Danfoss FC 300 Profibus Manual

Table of Contents

Advertisement

FC 300 Profibus
Bit (Hex)
Unit di-
PROFIBUS warning word (Par.
agnose
9-53)
bit
00000001
160
Connection with DP-master is not
ok
00000002
161
Timeout action active
00000004
162
FDL (Field-bus Data link Layer) is
not ok
00000008
163
Clear data command received
00000010
164
Actual value is not updated
00000020
165
Baudrate search
00000040
166
PROFIBUS ASIC is not transmitting
00000080
167
Initialising of PROFIBUS is not ok
00000100
152
Drive is tripped
00000200
153
Internal CAN error
00000400
154
Wrong configuration data from
PLC
00000800
155
Wrong ID sent by PLC
00001000
156
Internal error occurred
00002000
157
Not configured
00004000
158
Clear command received
00008000
159
Warning 34 active
Warning and Alarm Messages
There is a clear distinction between alarms and warnings. When there is an alarm, the frequency converter
will enter a fault condition. After the cause for the alarm has been cleared, the master will have to
acknowledge the alarm message before the frequency converter can start operating again. A warning, on
the other hand, may come when a warning condition appears, then disappear when conditions return to
normal, without interfering with the process.
Warnings
Warnings within the frequency converter are represented by a single bit within a warning word. A warning
word is always an active parameter. Bit status FALSE [0] means no warning, while bit status TRUE [1] means
warning. Any bit change in the warning word will be notified by a change of bit 7 in the status word.
Alarms
Following an alarm message the frequency converter will enter Fault condition. Only after the fault has been
alleviated and the master has acknowledged the alarm message by setting bit 7 in the control word, can the
frequency converter resume operation. Alarms within the frequency converter are represented by a single bit
within an alarm word. An alarm word is always an action parameter. Bit status FALSE [0] means no fault,
while bit status TRUE [1] means fault.

Fault Messages via DP Diagnosis

The standard DP function features an on-line diagnosis, which is active during DP initialisation as well as
data exchange mode.
82
Troubleshooting
FC 300
MG.33.C2.02 - VLT is a registered Danfoss trademark
FC 300
Bit (Hex)
Comm. option STW (Par. 16-84)
00000001
parameterization ok
00000002
configuration ok
00000004
clearmode active
00000008
baudrate search
00000010
waiting for parameterization
00000020
waiting for configuration
00000040
in data exchange
00000080
not used
00000100
not used
00000200
not used
00000400
not used
00000800
MCL2/1 connected
00001000
MCL2/2 connected
00002000
MCL2/3 connected
00004000
data transport active
00008000
not used
NB!:
Par. 16-84 Comm. Option STW is not part
of extended diagnosis.