FC 300 Profibus
Value
The value field contains the parameter value of the request. When the response is negative, the field
contains a corresponding error code. If the values consist of an odd number of bytes, a zero byte is
appended in order to maintain the word structure of the telegrams.
For a positive partial response, the parameter value field contains the following attributes:
Format = (Data Type or Byte, Word, Double Word)
Number of values = actual number of values
Value = Parameter value
For a negative partial response, the parameter value field contains the following:
Format = error (44H)
Number of values = 1
Value = error value = error number
Error Number for Drive Profile V3.0
When the parameter request is invalid, the frequency converter will return a corresponding error code.
The table below lists the full range of error codes.
Error codes for DP V1 parameter requests
Error code
Meaning
0x00
Unknown parameter
0x01
Parameter is read-only
0x02
Value out of range due to max/min value
0x03
Wrong sub-index
0x04
Parameter is no array
0x05
Wrong data type (wrong data length)
0x06
This parameter may not be set, only reset
0x07
Descriptive element is read-only
0x09
No description available (only value)
0x0b
Process control not possible
0x0f
No text array available (only value)
0x11
Not possible in current state
0x14
Value out of range due to drive state/configuration
0x15
Reply too long (more than 240 bytes)
0x16
Wrong parameter address (unknown or unsupported value for
attribute, element, par. number or sub-index or illegal combination)
0x17
Illegal format (for writing)
0x18
Value amount not consistent
0x65
Wrong axis: action not possible with this axis
0x66
Unknown service request
0x67
This service is not possible with multi parameter access
0x68
Parameter value can not be read from bus
50
How to Access FC 300 Parameters
MG.33.C2.02 - VLT is a registered Danfoss trademark
Additional Info
0
sub-index
sub-index
sub-index
0
0
sub-index
sub-index
0
0
0
0
sub-index
0
0
0
0
-
-
-
-