Operation
8.5 Fault and system messages
r0046
Missing enable signals
Display of the missing enable signals that are preventing the drive control from being commissioned
Bit
Signal name
18
OFF3 internal enable missing
26
Drive inactive or not operational
r0050
Active command data set (CDS)
Display of the active command data set (Command Data Set, CDS)
Bit
Signal name
00
CDS effective, bit 0
01
CDS effective, bit 1
02
CDS effective, bit 2
03
CDS effective, bit 3
Further notes can be found in the parameter description of the p0810, p0811, p0812, p0813 and r0836 parameters in the
List Manual.
The command data set selected via binector inputs p0810, p0811, p0812 and p0813 is displayed via r0836.
Diagnostic parameters for digital inputs/outputs
r0721
CU digital inputs terminal actual value
Display of the actual value on the digital inputs
Bit
Signal name
00
DI 0 (X122.1)
01
DI 1 (X122.2)
02
DI 2 (X122.3)
03
DI 3 (X122.4)
04
DI 4 (X132.1)
05
DI 5 (X132.2)
06
DI 6 (X132.3)
07
DI 7 (X132.4)
08
DI/DO 8 (X122.7)
09
DI/DO 9 (X122.8)
10
DI/DO 10 (X122.10)
11
DI/DO 11 (X122.11)
12
DI/DO 12 (X132.7)
13
DI/DO 13 (X132.8)
14
DI/DO 14 (X132.10)
15
DI/DO 15 (X132.11)
If a DI/DO is parameterized as output (p0728.x = 1), then r0721.x = 0 is displayed.
DI: Digital input
DI/DO: Bidirectional digital input/output
188
0-signal
1-signal
No
Yes
No
Yes
0-signal
1-signal
No
Yes
No
Yes
No
Yes
No
Yes
0-signal
1-signal
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents