Connection
Connection version
(see "Technical specifica‐
tions")
Infeed transformers
Recommended vector group
Converter output voltage
[kV]
Single connection, 12-pulse
2.3
3.3
4.16
The specified voltages and the necessary impulse withstand/test voltages for the transformer
1)
secondary windings with respect to ground. Since the transformers generally have temperature
evaluation systems in the windings, the specified test voltages are required for strengthened
insulation. If no control circuits have been installed in the windings, test voltages in accordance
with the basic insulation are sufficient.
Basic connection
2)
Parallel connection to increase the power rating
3)
3.5.8

Power Stack Adapter

The Power Stack Adapter (PSA) acts as the physical interface between the power unit and
the open-loop/closed-loop controller. This is where the galvanic isolation (electrical coupling
via light) between the power unit and the open-loop controller takes place. Data is exchanged
between the Power Stack Adapter and the Control Unit via the DRIVE-CLiQ high-speed serial
communication interface.
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
Single connection
Basic connection, 12-
pulse infeed
1 three-winding trans‐
former
Dy5 Dd0
Test voltage
[kV]
1)
23.6
33.6
38.9
Series connection of
Basic Line Modules
(option N15)
2 three-winding trans‐
formers
Dy5 Dd0
with primary shift +
7.5°
Dy5 Dd0
with primary shift - 7.5°
Transformer secondary voltage (no-load voltage)
[kV]
Parallel connection of Basic Line Module and Motor Module
on same DC bus
2 x 1.2
2)
2 x 1.7
2)
2 x 2.2
2)
3.5 Description of the components
Parallel connection of Basic Line Module
and Motor Module on same DC bus
Power increase using a parallel connec‐
tion; basic connection with sine-wave filter
2 three-winding or
1 five-winding transformer
Dy5 Dd0
with primary shift + 7.5°
Dy5 Dd0
with primary shift - 7.5°
-
2 x 1.7 (2x)
2 x 2.2 (2x)
Description
3)
3)
39