Siemens SINAMICS GM150 Operating And Installation Instructions page 225

Medium-voltage drive
Hide thumbs Also See for SINAMICS GM150:
Table of Contents

Advertisement

Removing the Power Stack Adapter
1. Disconnect all fiber-optic cables at the following terminals:
2. Disconnect all DRIVE-CLiQ cables directly at the connector on terminals X200-X202.
3. Use a slotted screwdriver to remove the green connectors for the control cables at the
4. Disconnect the connectors for the control cables from the terminal strip.
5. Remove the ground connection on the Power Stack Adapter chassis.
6. Use a Torx screwdriver to loosen the four fastening screws of the Power Stack Adapter.
7. Push the Power Stack Adapter upwards.
8. Remove the Power Stack Adapter.
Sending in the Power Stack Adapter
You can send in the defective Power Stack Adapter for a special examination. Further
information is contained in the note "Special examination of defective components (Page 209)".
Observe the following when you send in a component:
1. Close the fiber-optic cable connectors with blanking plugs.
2. Send the defective Power Stack Adapter only in the approved packaging.
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
– X21-X66
– X70-X79
– X81
Ensure that the disconnection is made only directly on the connector and not on the fiber-
optic cable.
following terminals:
– X210
– X221/222
– X231/232
– X241/242
Do not remove the screws.