5.
Terminate inverter's AC output wires inside the AC disconnect or junction box.
– Connect the AC equipment GND wire to the PE screw terminal (A).
– Connect the "WHITE" Neutral wire to the "N" screw terminal (B).
– Connect "BLACK" L1 wire to the "L1" terminal (C)
– Connect "RED" L2 wire to the "L2" terminal (D)
– Use a 3.5 mm flat blade screwdriver tighten the screw terminal to 10.5 in-lbs (1.2 Nm) of
torque for all above connections.
NOTICE!
AVIS!
NOTICE!
AVIS!
4.8.6

Inverter RS485 communication connections

WARNING!
AVERTISSEMENT!
38
Stranded copper wire should be checked so that all strands go into
the terminal opening.
Il conviendra d'inspecter le fil de cuivre multi-filaire afin de
s'assurer que tous ses brins sont insérés dans l'alésage de la
borne.
If the grid type with Neutral connection is selected, please double
check whether the Neutral wire is connected reliably. The un-
successful Neutral wire connection will make the unit fail to feed in
power to the grid because of the wrong phase voltage detection.
Si un réseau électrique avec connexion de neutre est choisie,
veuillez vérifier attentivement si le conducteur neutre est connecté
de manière fiable. Une connexion échouée du conducteur neutre
causera le manque d'énergie de l'appareil à cause de la détection
de tention en mauvais phase.
Read all of these instructions, cautions, and warnings for the Delta
M series inverter and associated PV array documentation.
Lisez toutes les instructions, rubriques Prudence et Avertissement
de l'onduleur Delta M series , ainsi que la documentation sur le
panneau photovoltaïque associé.