Grid-tie transformerless solar inverter (170 pages)
Summary of Contents for Delta M100A 280
Page 1
Graphical Installation Guide Solar inverter M100A_280 (Delta part number RPI104M280000, product version 0) European Union Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 2
Electronics (Netherlands) B.V. must include the annota- tion: "Translation of the original operation manual". and DSS software version 6.0 or higher Delta Electronics (Netherlands) B.V. The Delta part number can be found on the type plate of Tscheulinstraße 21 the inverter. 79331 Teningen...
Page 3
M50A _260 P/N: RPI503260000 200-1000Vdc, MPPT 390-900Vdc MAX Idc: 26A*6 MPPT, 1000Vdc max MAX Idc: 50A*6 MPPT 220/380Vac, 230/400Vac 3P4W/3P3W, 50/60Hz 83.4A max., cosφ 0.8ind ~ 0.8 cap 50kW/50kVA nom, 50kW/55kVA max IP Code IP66 O....0 Product version Changes to the previous model This is a new product.
● All repair work on the inverter must be carried out by Delta Electronics. Otherwise the warranty will be void. Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 5
Safety Instructions ● Warning notices, warning symbols and other mark- ings attached to the inverter by Delta Electronics must not be removed. ● To avoid the risk of arcing, do not disconnect cables when the inverter is under load. ●...
Scope of Delivery MOU-H INV-I INV-Q INV-X Do not use any damaged components. Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 7
Scope of Delivery DC-P+ AC-C1 Amphenol H4 – 4/6 mm DC+ (H4CFC4D●MS) DC-P– AC-PE Amphenol H4 – 4/6 mm DC– (H4CMC4D●MS) DC-T AC-C2 DC-B Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Accessories must be ordered separately. Windows PC 0,25 ... 1,5 mm RS485/USB Adapter A Windows PC with a RS485/USB adapter is required. Delta Service Software (DSS) must be installed on the Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Information on the type plate Risk of death due to electric shock Potentially fatal voltage is present inside the inverter during operation and this voltage remains for 60 seconds after the power supply is disconnected. 60 seconds Before working on the inverter, read the supplied manual and follow the instructions provided.
Page 10
Dimensions 144,5 263,4 max. 1,8 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 11
Dimensions Sub-1G Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Wall mounting Ø 6,5 mm 77 kg Ø 8,5 mm / 10 Nm Ø 8,5 mm / 10 Nm Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Floor mounting Ø13 mm 24,5 Nm 77 kg Ø13 mm Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 16
Mounting SWITCH 1 SWITCH 2 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 17
Communication card RS485 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 18
RS485 RS485 CAT5 / CAT6 Ø 7,2 / 8,0 / 10,0 mm; 0,25 ... 1,5 mm (1) RS485 terminal block • (2) DIP switch for RS485 termination resistor Switch on the RS485 terminator resistor of the data log- ger or connect a termination resistor. If the data logger does not have an integrated RS485 terminator resistor, connect the data logger in the middle Data logger...
Digital inputs CAT5 / CAT6 Ø 7,2 / 8,0 / 10,0 mm; 0,25 ... 1,5 mm The event at which the relays of the dry contacts trip can be set with the Delta Service software. – – External power-off –...
Page 20
Connect a PC Delta Service Software (DSS ) RS485 RS485/USB Adapter Windows PC Connect the PC to the inverter via the RS485/USB adapter. Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 21
Connecting the grid (AC) AC-C1 + AC-C2 D1.1 D1.2 D1.3 D1.4 D2.1 D2.2 D2.3 AC-C2 d [mm] M [Nm] P [mm] d [mm] M [Nm] P [mm] 72 ... 77 mm 10 Nm 6,5 ... 4,5 mm D2.1 25 ... 28 mm 6,5 ...
Page 22
Connecting the grid (AC) M10 Hex / 42,4 Nm 270 mm 195 mm M10 / 24,5 Nm AC-C1 AC-PE M8 / 14,7 Nm 70 ... 240 mm 70 ... 240 mm Al se 30 mm L1 / L2 / L3 / N <...
Connecting the Solar Modules (DC) DC-P+ DC-P– Amphenol H4 – 4/6 mm Amphenol H4 – 4/6 mm DC+ (H4CFC4D●MS) DC– (H4CMC4D●MS) DC-T DC-B DC-B Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 24
Commissioning SWITCH 1 SWITCH 2 Delta Service Software (DSS ) Windows PC The inverter must be supplied with alternating current Start the software and commission the inverter. (grid) and/or direct current (solar modules). Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Page 25
Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03...
Technical data Input (DC) M100A 12.7 kW / 110 kW Maximum input power (per MPP Tracker/total) 100 kW Rated power 200 to 1000 V Input voltage range for operation 1100 V Maximum input voltage 610 V Nominal voltage Number of MPP trackers 200 to 1000 V Total MPP input voltage range MPP input voltage range with full power...
Page 27
RS485, Sub-1G (optional), Wi-Fi (optional) Communication Modbus RTU Communication protocols General specifications M100A M100A_280 Delta model name RPI104M280000 Delta part number -25 to +60 °C Overall operating temperature range 0 to 100%, non-condensing Reltaive humidity 4000 m above sea level Max.