7.6

Connecting the communication card

The connections for RS485, the dry contacts, the
digital inputs and the external power-off (EPO)
are all on the communication card. This means
that the installation work can be combined.
NOTICE
Water ingress.
► All sealing caps removed during installa-
tion should be stored for later use (e.g. (e.g.
transportation or storage).

7.6.1 Connections on the communication card

6
5
Fig. 7.1:
Components of the communication card
1 Digital inputs and external power-off (terminal block)
2 Power supply for internal fan 1
2 DIP switch for the RS485 termination resistor
3 2 x dry contacts (terminal block)
4 RS485 (terminal block)
5 Protection against electromagnetic interference (EMI)
Connection
2x RS485 (DATA+ and DATA–)
1x VCC (12 V, 0.5 A)
6x digital inputs
2x dry contacts
1x external power-off (EPO)
Table 7.2.: Connections on the communication card
Installation and operation manual M70A_260 Flex RPI703M26000 EU V1.1 EN 2022-08-02
1
4
Connection type
Terminal block
Terminal block
Terminal block
Terminal block
Terminal block
Cable type
Cable diameter
Wire cross section
Table 7.3.: Specification of the communication cable
The communication cable is required for connection to the follow-
ing units:
Data logger
External alarm unit
Ripple control receiver
External power-off
Lay the communication cable with a suitable clearance to the AC
and DC cables to prevent interference in the data connection.
2
3
7 Installation
Connecting the communication card
Shielded and twisted pair cable
(CAT5 or CAT6)
2 x 7.2 / 8 / 10 mm
2
0.25 ... 1.5 mm
65