Electrode axis

1 Electrode axis
Figure 12: Orientation of the electrode axis
The flowmeter sensor should be mounted in the piping in such a
manner that the electrode axis is oriented as horizontally as
possible.
A maximum deviation of 45° from the horizontal position is
permissible.

Mounting position

Figure 13: Mounting position
Vertical installation for measuring abrasive materials,
A
preferably with flow in upward direction.
For a horizontal installation, the meter tube must always be
B
completely filled with the measuring medium.
Provide for a slight incline of the connection for degassing.
Note
For hygienic applications, the vertical mounting position is
preferred.
For a horizontal mounting position, make sure that the sensor is
installed to be self-draining.

Minimum spacing of the devices

Spacing D: ≥ 1.0 m (3.3 ft) for Design Level 'A',
≥ 0.7 m (2.3 ft) for Design Level 'B'
HygienicMaster
Spacing D: ≥ 1.0 m (≥ 3.3 ft)
Figure 14: Minimum spacing
In order to prevent the devices from interfering with each
other, a minimum distance as presented in Minimum spacing
of the devices must be maintained between the devices.
The sensor must not be operated in the vicinity of powerful
electromagnetic fields, e.g., motors, pumps, transformers,
etc. A minimum spacing of approx. 1 m (3.28 ft) must be
maintained.
For installation on or to steel parts (e.g. steel brackets), a
minimum spacing of 100 mm (3.94 in
These values have been calculated on the basis of IEC 801-2
or IEC TC77B
FEH
xxx
D
G12063
)
must be maintained.