ABB ProcessMaster FEP630 Series Operating Instruction page 92

Electromagnetic flowmeter
Hide thumbs Also See for ProcessMaster FEP630 Series:
Table of Contents

Advertisement

92
FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D
... 8 Operation
... Parameter descriptions
Menu / parameter
Input/Output / ...Dig.Out 51/52 / ...Setup Logic Output
Logic Output Action
Active Mode
Input/Output / ...Dig.Out 51/52 / ...Alarm Config
General Alarm
Qv Volumeflow Max
Qv Volumeflow Min
EPD
TFE
Gas Bubble
Conductivity
Sensor Temperature
In house Temp
Input/Output / ...Dig.Out V1/V2
Input/Output / ...Dig. Out V3/V4
Mode
...Setup Logic Output
...Alarm Config
Description
Selection of binary output function.
See description '„Input/Output / ...Dig.Out 41/42 / ...Setup Logic Output'.
Select switching properties for the binary output.
Active High: Normally open
Active Low: Normally closed
Default setting: Active High.
Selection of error messages signaled via the binary output 51 / 52.
Only if the parameter 'Logic Output Action' is set to Alarm Signal.
Selection of operating mode for the digital output V1 / V2 or V3 / V4.
Off: Digital output deactivated.
Logic: Digital output functions as binary output (for function see parameter '...Setup Logic Output').
The digital outputs V1 / V2 and V3 / V4 are only available if the corresponding plug-in cards are present!
Selection of submenu '...Setup Logic Output' using
Only available if 'Mode / Logic' has been selected.
Selection of submenu '...Alarm Config' using
Only available if 'Mode / Logic' has been selected.
.
.