Menu: Easy Setup

Menu / parameter
Easy Setup
Language
Unit Volumeflow Qv
Qv Max 1
Unit Vol. Totalizer
Dig.Out 41/42 Mode
Pulses per Unit
Pulse Width
Upper Frequency
Damping
Curr.Out at Alarm
Low Alarm
High Alarm
System Zero
Description
Selection of the menu language (German, English, French, Spanish, Italian, Chinese, Portuguese).
Selection of the unit for the volume flow (for example for the parameters Qv
process value).
Default setting: l/min
Table 1: Units for the volume flow on page 78
Setting the upper range value 1 (Measuring range = 0 to Qv Max 1) for the volume flow for forward flow and reverse flow .
Default setting: 1 × Q
DN
max
Selection of the unit for the volume totalizers and the pulse outputs.
Default: l (liter)
Table 4: Units for the volume totalizer on page 78
Selection of the operating mode for the digital output 41 / 42.
Off: Digital output 41 / 42 deactivated.
Logic: Digital output 41 / 42 as a binary output (e.g. as an alarm output).
Pulse: Digital output 41 / 42 as a pulse output. In pulse mode, pulses are output per unit (e.g. 1 pulse per m
Frequency: Digital output 41 / 42 as a frequency output. In frequency mode, a frequency is issued that is proportional to
the flow rate. The maximum frequency can be configured in accordance with the upper range value.
Default setting: Pulse
Set pulses per volume or per mass flow unit, and the pulse width for the digital output operating mode 'Pulse'. The pulse
value and pulse width are interdependent and calculated dynamically (pulses per unit: 1 to 10000 / s, pulse width:
0.1 to 2000 mS).
Only available if a digital output has been configured as a pulse output, and the volume flow or mass flow has been selected
as the process variable to be output.
Sets the upper range value frequency for the digital output operating mode 'Frequency'. The entered value (0 to 10500 Hz)
corresponds to 100 % flow.
Only available if a digital output has been configured as a frequency output, and the volume flow or mass flow has been
selected as the process variable to be output.
Select the damping.
The value set here (0.02 to 60 s) refers to 1 τ (Tau). The value refers to the response time for a step flowrate change. It
affects the instantaneous value in the display and at the current output.
Default setting: 1 second
Selection of status of the current output in error condition.
The output 'Low Alarm' or 'High Alarm' current is set in the subsequent menu.
Setting the current (3.5 to 3.6 mA) for low alarm.
Setting the current (21 to 22.6 mA) with high alarm.
Starts the automatic zero point balancing using
Note
Prior to starting the zero point adjustment, make sure that:
There is no flow through the sensor (close all valves, shut-off devices etc.)
The sensor must be filled completely with measuring medium for measurement.
/ Qv
Max
Max
. Automatic zero point balancing takes approx. 60 seconds.
DN and for the corresponding
3
).
79