FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D
Menu / parameter
Input/Output / ...Dig.Out 41/42 / ...Alarm Config
General Alarm
Qv Volumeflow Max
Qv Volumeflow Min
EPD
TFE
Gas Bubble
Conductivity
Sensor Temperature
In house Temp
Input/Output / ...Dig.Out 51/52
Mode
Outp. Flow Direction
...Setup Logic Output
...Alarm Config
Description
Select error messages signaled via the binary output 41 / 42.
Only if the parameter 'Logic Output Action' is set to Alarm Signal.
Selection of the operating mode for the digital output 51 / 52. The following operating mode 'Follow DO 41/42, <90° Shift,
180° Shift' is only available if the digital output 51 / 52 has been configured as a pulse output.
Off: Digital output deactivated.
Logic: Digital output functions as binary output (for function see parameter '...Setup Logic Output').
Follow DO 41/42: The digital output 51 / 52 follows the pulses from the digital output 41 / 42. The function depends on
the setting of the parameter 'Outp. Flow Direction'.
90° Shift: 90° phase-shifted output of the same pulses as for digital output 41 / 42.
180° Shift: 180° phase-shifted output of the same pulses as for digital output 41 / 42.
Selection of flow direction in which the pulse / frequency output issues the selected process value.
The parameter is only available if Follow DO 41/42 has been configured for digital output 51 / 52 in parameter 'Mode'.
No pulses are issued if 'Forward & Reverse' is selected. Only digital output 41 / 42 is active.
When 'Forward' is selected, pulses for forward flow are issued at digital output 41 / 42 and pulses for reverse flow at
digital output 51 / 52 .
When 'Reverse' is selected, pulses for forward flow are issued at digital output 41 / 42 and pulses for reverse flow at
digital output 51 / 52
Selection of submenu '...Setup Logic Output' using
Only available if 'ModeLogic' has been selected.
Selection of submenu '...Alarm Config' using
Only available if 'ModeLogic' has been selected.
.
.
91