FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D
... 8 Operation
... Parameter descriptions
Menu / parameter
Communication / ...Modbus
Address
IEEE Format
Baud Rate
Parity
Stop Bits
Response Delay
Communication / ...Profibus
Address
Ident Nr. Selector
Comm State
Baud Rate
PB Manufacturer ID
Description
Setting the Modbus device address (1 to 127).
Selection of the byte order for the Modbus communication.
Enabled: If the IEEE format is activated, the data words are sent in the 'little endian' format with the lowest value word
first.
Disabled: If the IEEE format is deactivated, the data words are sent in the standard Modbus 'bigendian' format.
Factory setting: Enabled.
Selection of the transmission speed (baud rate) for the Modbus communication.
Factory setting: 9600 baud.
Selection of the parity for the Modbus communication.
Factory setting: Odd.
Selection of the stop bits for the Modbus communication.
Factory setting: One stop bit
Setting of the pause time in milliseconds after receiving a Modbus command. The device sends a response no earlier than
expiration of the set pause time.
Factory setting: 10 ms
Set the PROFIBUS DP® device address (1 to 126).
Display the PROFIBUS DP® identification number
9700: 1xAI
9740: 1xAI + 1xTOT
3432: ABB-specific
Display the PROFIBUS communication status.
Offline: No PROFIBUS® communication.
Stop: Bus active, device not active.
Clear: Device is being initialized.
Operate: Cyclic communication is active.
Display the transmission speed (baud rate) for the PROFIBUS® communication.
The baud rate is automatically detected and does not need to be configured manually.
Display the PROFIBUS DP® manufacturer ID
26: ABB