96
FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D
... 8 Operation
... Parameter descriptions
Menu / parameter
Communication / ...Modbus
Address
IEEE Format
Baud Rate
Parity
Stop Bits
Response Delay
Communication / ...Profibus
Address
Ident Nr. Selector
Comm State
Baud Rate
PB Manufacturer ID
Description
Setting the Modbus device address (1 to 127).
Selection of the byte order for the Modbus communication.
•
Enabled: If the IEEE format is activated, the data words are sent in the 'little endian' format with the lowest value word
first.
•
Disabled: If the IEEE format is deactivated, the data words are sent in the standard Modbus 'bigendian' format.
Factory setting: Enabled.
Selection of the transmission speed (baud rate) for the Modbus communication.
Factory setting: 9600 baud.
Selection of the parity for the Modbus communication.
Factory setting: Odd.
Selection of the stop bits for the Modbus communication.
Factory setting: One stop bit
Setting of the pause time in milliseconds after receiving a Modbus command. The device sends a response no earlier than
expiration of the set pause time.
Factory setting: 10 ms
Set the PROFIBUS DP® device address (1 to 126).
Display the PROFIBUS DP® identification number
•
9700: 1xAI
•
9740: 1xAI + 1xTOT
•
3432: ABB-specific
Display the PROFIBUS communication status.
•
Offline: No PROFIBUS® communication.
•
Stop: Bus active, device not active.
•
Clear: Device is being initialized.
•
Operate: Cyclic communication is active.
Display the transmission speed (baud rate) for the PROFIBUS® communication.
The baud rate is automatically detected and does not need to be configured manually.
Display the PROFIBUS DP® manufacturer ID
•
26: ABB