Tightening Torques For Hygienicmaster With Variable Process Connections; Parameterization Overview (Factory Settings) - ABB ProcessMaster FEP630 Series Operating Instruction

Electromagnetic flowmeter
Hide thumbs Also See for ProcessMaster FEP630 Series:
Table of Contents

Advertisement

FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D

Tightening torques for HygienicMaster with variable process connections

Nominal diameter
[mm]
DN 3 to DN 10
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50
DN 65
DN 80
DN 100

Parameterization overview (factory settings)

Parameter
Sensor Tag
Sensor Location Tag
Qv Max 1
Unit Volumeflow Qv
Unit Vol. Totalizer
Pulses per Unit
Pulse Width
Damping
Operating mode Digital output 41 / 42 Off, Binary output, Pulse output, Frequency output
Operating mode Digital output 51 / 52
Curr.Out 31/32
Curr.Out at Alarm
Current at flow rate> 103 % (I=20.5 mA) Off (current output remains at 20.5 mA), High Alarm, Low
Low flow cutoff
Empty pipe detection
[in]
⅜ in
½ in
¾ in
1
1 ¼ in
1 ½ in
2
2 ½ in
3
4
Value range
Alphanumeric, maximum 20 characters.
Alphanumeric, maximum 20 characters.
Depending on the nominal diameter of the sensor.
l/s; l/min; l/h; ml/s; ml/min; m3/s; m3/min; m3/h; m3/d;
hl/h; g/s; g/min; g/h; kg/s; kg/min; kg/h; kg/d; t/min;
t/h; t/d
m3; l; ml; hl; g; kg; t
1 to 10000
0.1 to 2000 ms
0.02 to 60 s
Off, Binary output, pulse output (follows digital output
41 / 42, 90 ° or 180 ° out of phase)
4-20mA FWD/REV, 4-20mA FWD, 4-12-20 mA
High Alarm 21 to 23 mA or Low Alarm 3.5 to 3.6 mA
Alarm ,
0 to 10 %
On / Off
Maximum tightening torque
Set to Q
DN in accordance with Measuring range
max
Digital output 41/42 as pulse output for forward flow
Digital output 51 / 52 as binary output for output of
151
[Nm]
8
10
21
31
60
80
5
5
15
14
Factory setting
None
None
table on page 60.
l/min
Liter (l)
1
100 ms
1
and reverse flow
the flow direction.
4-20mA FWD/REV
High Alarm, 21.8 mA
Off
1 %
Off