4.2. Quick Set-up

4.2.1. Quick Menu Mode
Parameter Data
The graphical display (GLCP) provides access
to all parameters listed under the Quick Me-
nus. The numeric display (NLCP) only provides
access to the Quick Setup parameters. To set
parameters using the [Quick Menu] button -
enter or change parameter data or settings in
accordance with the following procedure:
1.
2.
3.
4.
5.
6.
7.
8.
Select [My Personal Menu] to display only the parameters, which have been pre-selected and
programmed as personal parameters. For example, an AHU or pump OEM may have pre-pro-
grammed these to be in My Personal Menu during factory commissioning to make on-site
commissioning / fine tuning simpler. These parameters are selected in
Up to 20 different parameters can be programmed in this menu.
If [No Operation] is selected in
27 is necessary to enable start.
If [Coast Inverse] (factory default value) is selected in
to +24V is necessary to enable start.
Select [Changes Made] to get information about:
Select [Loggings] to get information about the display line read-outs. The information is shown
as graphs.
Only display parameters selected in par. 0-20 and par. 0-24 can be viewed. It is possible to store
up to 120 samples in the memory for later reference.
Efficient Parameter Set-up for HVAC Ap-
plications
The parameters can easily be set up for the vast majority of the HVAC applications only by using
the [Quick Setup] option.
Press Quick Menu button
Use the [▲] and [▼] buttons to find
the parameter you want to change
Press [OK]
Use [▲] and [▼] buttons to select the
correct parameter setting
Press [OK]
To move to a different digit within a
parameter setting, use the [◀] and
[▶] buttons
Highlighted area indicates digit se-
lected for change
Press [Cancel] button to disregard
change, or press [OK] to accept
change and enter the new setting
par. Terminal 27 Digital Input
the last 10 changes. Use the up/down navigation keys to scroll between the last 10
changed parameters.
the changes made since default setting.
MG.11.F1.02 - VLT
®
is a registered Danfoss trademark
4. How to Programme
Example of Changing Parameter Data
Assume parameter
22-60, Broken Belt Func-
tion
is set to [Off]. However, you want to
monitor the fan-belt condition - non- broken
or broken - according to the folowing proce-
dure:
1.
Press Quick Menu key
2.
Choose Function Setups with the [▼]
button
3.
Press [OK]
4.
Choose Application Settings with the
[▼] button
5.
Press [OK]
6.
Press [OK] again for Fan Functions
7.
Choose Broken Belt Function by
pressing [OK]
8.
With [▼] button, choose [2] Trip
The frequency converter will now trip if a bro-
ken fan-belt is detected.
par. 0-25 Personal Menu
, no connection to +24 V on terminal
par. Terminal 27 Digital Input
4
.
, a connection