3. How to Install

3.6.14. Fuses

Branch circuit protection
In order to protect the installation against electrical and fire hazard, all branch circuits in an in-
stallation, switch gear, machines etc., must be short-circuited and over-current protected accord-
ing to national/international regulations.
Short-circuit protection
3
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard.
Danfoss recommends using the fuses mentioned below to protect service personnel and equip-
ment in case of an internal failure in the drive. The frequency converter provides full short-circuit
protection in case of a short-circuit on the motor output.
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation.
The frequency converter is equipped with an internal over-current protection that can be used for
upstream overload protection (UL-applications excluded), see par. 4-18. Moreover, fuses or circuit
breakers can be used to provide the over-current protection in the installation. Over-current pro-
tection must always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000
A
rms
Fuse Tables
Size/
Type
P110
P132
P160
P200
P250
Table 3.5: D enclosures, 380-480 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/
110 Type T indicator fuses of the same size and amperage may be substituted for external use
**Any minimum 480 V UL listed fuse with associated current rating may be used to meet UL
requirements.
Size/Type
P110
P132
P160
P200
P250
P315
Table 3.6: D enclosures, 525-600 V
54
(symmetrical).
Buss-
Buss-
mann
mann
SIBA
E1958
E4273
E180276
JFHR2*
T/
RKI/JDDZ
*
JDDZ**
FWH-
JJS-
2028220-
300
300
315
FWH-
JJS-
2028220-
350
350
315
FWH-
JJS-
206xx32-
400
400
400
FWH-
JJS-
206xx32-
500
500
500
FWH-
JJS-
206xx32-
600
600
600
Bussmann
E125085
JFHR2
170M3017
170M3018
170M4011
170M4012
170M4014
170M5011
MG.11.F1.02 - VLT
Buss-
Ferraz-
LittelFuse
mann
Shawmut
E71611
E4274
E60314
JFHR2**
JFHR2**
JDDZ**
L50S-300
A50-P300
NOS-
L50S-350
A50-P350
NOS-
L50S-400
A50-P400
NOS-
L50S-500
A50-P500
NOS-
L50S-600
A50-P600
NOS-
SIBA
Amps
E180276
JFHR2
315
2061032.315
350
2061032.350
350
2061032.350
400
2061032.400
500
2061032.500
550
2062032.550
®
is a registered Danfoss trademark
®
VLT
HVAC DRIVE High Power
Operating Instruction
Bussmann
Internal
E125085
Option
H/
JFHR2*
Bussmann
170M3017
170M3018
300
170M3018
170M4016
350
170M4012
170M4016
400
170M4014
170M4016
500
170M4016
170M4016
600
Ferraz-Shawmut
E76491
JFHR2
6.6URD30D08A0315
6.6URD30D08A0350
6.6URD30D08A0350
6.6URD30D08A0400
6.6URD30D08A0500
6.6URD32D08A0550