Danfoss VLT HVAC Drive FC 100 Operating Instructions Manual page 70

High power
Hide thumbs Also See for VLT HVAC Drive FC 100:
Table of Contents

Advertisement

4. How to Programme
After pressing [Quick Menu], the different areas in the Quick Menu are listed. See also illustration
6.1 below and tables Q3-1 to Q3-4 in the following
Example of using the Quick Setup option
Assume you want to set the Ramp Down Time
to 100 seconds!
1.
2.
4
3.
4.
5.
6.
7.
8.
The new ramp-down time is now set to 100
seconds.
It is recommended to do the set-up in the or-
der listed.
Par. Designation
0-01 Language
1-20 Motor Power
1-21 Motor Power*
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
3-41 Ramp 1 Ramp up Time
3-42 Ramp 1 Ramp down Time [s]
4-11 Motor Speed Low Limit
4-12 Motor Speed Low Limit*
4-13 Motor Speed High Limit
4-14 Motor Speed High Limit*
3-11 Jog Speed*
5-12 Terminal 27 Digital Input
5-40 Function Relay
Table 4.1: Quick Setup parameters
70
Press [Quick Setup]. The first
0-01 Language
in Quick Setup ap-
pears
Press [▼] repeatetly until
par. 3-42
Ramp 1 Ramp Down Time
with the default setting of 20 sec-
onds
Press [OK]
Use the [◀] button to highlight the
3rd digit before the comma
Change '0' to '1' by using the [▲] but-
ton
Use the [▶] button to highlight the
digit '2'
Change '2' to '0' with the [▼] button
Press [OK]
[Unit
s]
[kW]
[HP]
[V]
[Hz]
[A]
[RPM]
[s]
[RPM]
[Hz]
[RPM]
[Hz]
[Hz]
MG.11.F1.02 - VLT
Function Setups
NB!
A complete description of the
function is found in the param-
eter sections of these Operating
par.
Instructions.
appears
Illustration 4.1: Quick Menu view.
The QUICK Setup menu gives access to the 12
most important setup parameters of the drive.
After programming the drive will, in most ca-
ses be ready for operation. The 12 (see foot-
note) Quick Menu parameters are shown in
the table below. A complete description of the
function is given in the parameter sections of
this manual.
*The display showing depends on choices
made in parameter 0-02 and 0-03. The default
setting of parameters 0-02 and 0-03 depends
on which region of the world the frequency
converter is supplied to but can be re-pro-
grammed as required.
®
is a registered Danfoss trademark
®
VLT
HVAC DRIVE High Power
Operating Instruction
section.

Advertisement

Table of Contents
loading

Table of Contents