2. Safety Instructions and General Warning

2.1.2. High Voltage

2

2.1.3. Safety Instructions

2.1.4. General Warning
10
The voltage of the frequency converter is dangerous whenever the frequency con-
verter is connected to mains. Incorrect installation or operation of the motor or
frequency converter may cause damage to the equipment, serious personal injury
or death. The instructions in this manual must consequently be observed, as well as
applicable local and national rules and safety regulations.
Installation in high altitudes
At altitudes above 2 km, please contact Danfoss Drives regarding PELV.
Make sure the frequency converter is properly connected to earth.
Protect users against supply voltage.
Protect the motor against overloading according to national and local regulations.
Motor overload protection is not included in the default settings. To add this function,
Motor thermal protection
set parameter 1-90
North American market: ETR functions provide class 20 motor overload protection, in
accordance with NEC.
The earth leakage current exceeds 3.5 mA.
The [OFF] key is not a safety switch. It does not disconnect the frequency converter from
mains.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been dis-
connected from mains.
Also make sure that other voltage inputs have been disconnected, such as load-
sharing (linkage of DC intermediate circuit), as well as the motor connection for
kinetic back-up.
When using the frequency converter: wait at least 40 minutes.
Shorter time is allowed only if indicated on the nameplate for the specific unit.
Leakage Current
The earth leakage current from the frequency converter exceeds 3.5 mA. To ensure
that the earth cable has a good mechanical connection to the earth connection (ter-
minal 95), the cable cross section must be at least 10 mm
terminated separately.
Residual Current Device
This product can cause a D.C. current in the protective conductor. Where a residual
current device (RCD) is used for extra protection, only an RCD of Type B (time de-
layed) shall be used on the supply side of this product. See also RCD Application
Note MN.90.Gx.02 (x=version number).
Protective earthing of the frequency converter and the use of RCD's must always
follow national and local regulations.
MG.11.F1.02 - VLT
ETR trip
to value
or
2
®
is a registered Danfoss trademark
®
VLT
HVAC DRIVE High Power
Operating Instruction
ETR warning
. For the
or 2 rated earth wires